RA-912F Portable Comprehensive SF6 Multi Analyzer
RA-912F allows the determination of up to three quality parameters with only one measurement:
-
- SF6 concentration (%)
- Moisture concentration
- SO2 concentration (ppm)
RA-912F SF6 Multi Analyzer based on Thermal conductivity measuring SF6 purity of principle, only SF6 has spectral band absorption characteristics, interference from other components, to fully meet all kinds of electrical equipment using sulfur hexafluoride-filled with gases such as N2 or CF4;
Unique advanced cross-sensitivity to measure the decomposition algorithm, a large number of laboratory data foundation, integration of linear algebra algorithms to calculate the results more accurate;
Classic polymer film humidity measurement SF6, when ambient humidity changes, the moisture sensitive components of the dielectric constant is changed, a corresponding change in the output electrical signal.
-
- Using the principle of SF6 gas spectral absorption measurements, rapid, without the interference of other gas components to better meet the needs of the site.
- SF6 purity mass ratio (g / g), volume ratio (mol/mol) switch at any time to display, can be directly controlled national standard, eliminating the volume and mass ratio conversion link.
- Massive experimental data, based on real-time traffic temperature compensation.
- Unique patented drying protection device.
- Boot-up zero, the slope of the self-calibration.
- Built-in gas filtration system
- Each measuring gas path individually designed to ensure accuracy, independent regulation is more suitable for field use.
- TFT touchscreen
- Built-in printer
Technical data | |
---|---|
Dimensions: | L 406 mm, W 538 mm, H 269 mm |
Weight | 15 kg |
Input pressure | 0.2 - 35 bar |
Operating temperature: | -20 °C to +50 °C |
Ambient moisture: | 15% up to 90 % relative moisture, non condensing during operation |
Operating voltage: | 100-240 VAC, 50/60Hz |
Number of measured values to be stored: max. | 500 |
Interface: | USB |
Purity | Moisture | SO2 | H2s | CO | |
---|---|---|---|---|---|
Measuring principle | Thermal conductivity | Electronic moisture measurement (capacitive) | Electrochemical reaction | Electrochemical reaction | Electrochemical reaction |
Measuring range | 0 - 100 vol.% | -80 to +20 °C | 0 to 100 ppm 0 to 10 ppm 0 to 2000ppm | 0 to 100 ppm | 0 to 500 ppm |
Measuring accuracy | ±2 %(F.S) | ±2 ℃ | ±5 % μL/L | ±5 % μL/L | ±5 % μL/L |
Flow rate | 250 to 350 mL/min Recommend 300 mL/min | 300 to 900 mL/min Recommend 500 mL/min | 100 to 120 mL/min Recommend 100 mL/min | 100 to 120 mL/min Recommend 100 mL/min | 100 to 120 mL/min Recommend 100 mL/min |
Reaction time | < 30 s | < 3 min | < 60 s | < 60 s | < 60 s |
Recommended calibration interval | every one years | every one years | every one years | every one years | every one years |